5.2 Function Code Tables 
 
 
Control method and Data setting range 
Terminal [Y1] 
to [Y4], 
[Y5A/C], 
[30A/B/C] 
Terminal 
[Y1A/B/C] to 
[Y4A/B/C] 
 
30 (1030): Lifetime alarm  “LIFE” 
 
31 (1031): Frequency (speed) detected 2  “FDT2” 
 
33 (1033): Reference loss detected  “REF OFF” 
 
35 (1035): Inverter outputting  “RUN 2” 
 
36 (1036): Overload prevention controlling  “OLP” 
 
37 (1037): Current detected  “ID” 
38 (1038): Current detected 2  “ID2” 
39 (1039): Current detected 3  “ID3” 
41 (1041): Low current detected  “IDL” 
 
42 (1042): PID alarm  “PID-ALM” 
43 (1043): Under PID control  “PID-CTL” 
44 (1044): Under sleep mode of PID control    “PID-STP” 
 
45 (1045): Low torque detected  “U-TL” 
46 (1046): Torque detected 1  “TD1” 
47 (1047): Torque detected 2  “TD2” 
 
48 (1048): Motor 1 selected  “SWM1” 
49 (1049): Motor 2 selected  “SWM2” 
50 (1050): Motor 3 selected  “SWM3” 
51 (1051): Motor 4 selected  “SWM4” 
 
52 (1052): Forward rotation    “FRUN” 
53 (1053): Reverse rotation    “RRUN” 
 
54 (1054): Under remote mode  “RMT” 
 
56 (1056): Motor overheat detected by thermistor  “THM” 
 
57 (1057): Mechanical brake control    “BRKS” 
 
58 (1058): Frequency (speed) detected 3  “FDT3” 
 
59 (1059): Current input wire break detection (terminal [C1] and [C2])   
  “C1OFF” 
 
70 (1070): Speed valid    “DNZS” 
 
71 (1071): Speed agreement  “DSAG” 
 
72 (1072): Frequency (speed) arrival 3  “FAR3” 
 
76 (1076): Speed mismatch  “PG-ERR” 
 
77 (1077): Low DC link bus voltage detection  “U-EDC” 
 
79 (1079): During decelerating at momentary power failure  “IPF2” 
 
82 (1082): Positioning complete    “PSET” 
 
84 (1084): Maintenance timer counted up    “MNT” 
 
87 (1087): Frequency arrival and detected  “FARFDT” 
 
89 (1089): Magnetic pole position detection complete signal    “PTD”