5.2 Function Code Tables
5-23
FUNCTION CODES
Chap 5
Function
code
Name
Control method and Data setting range
Change when
running
Data copying
Factory
default
Related page
H76
Torque limiter (Braking)
(Frequency rising limiter for
braking)
0.0 to 599.0 Hz
Y
Y
5.0
5-239
H77
Service life of DC link bus
capacitor
0 to 87600 hours (updated in 10 hour units)
Y
N
87600
5-239
H78
Maintenance interval (M1)
0 (Disable), 1 to 99990 hours (updated in 10 hour units)
Y
N
87600
5-240
H79
Preset startup count for
maintenance (M1)
0 (Disable), 1 to 65535 times
Y
N
0
5-241
H80
Output current fluctuation
damping gain for motor 1
0.00 to 1.00
Y
Y
0.20
5-241
H81
Warning selection 1
0000 to FFFF (in hexadecimal)
Y
Y
0000
5-242
H82
Warning selection 2
Y
Y
0000
H83
Warning selection 3
Y
Y
0000
H84
Pre-excitation (Level)
100 to 400 % (Motor rated magnetizing current for 100 %)
Y
Y
100
5-246
H85
(Braking time)
0.00: Disable
0.01 to 30.00 s
Y
Y
0.00
H86
For adjustment by
manufacturer *9
0 to 2
Y
Y
0
5-248
H89
For adjustment by
manufacturer *9
0, 1
Y
Y
1
5-248
H90
For adjustment by
manufacturer *9
0, 1
Y
Y
0
5-248
H91
Current input wire break
detection
0.0 (Alarm disable): 0.1 to 60.0 s
Y
Y
0.0
5-248
H92
Continuous running at the
momentary power failure (P)
0.000 to 10.000 times
999: Manufacturer adjustment value
Y
Y1
Y2
999
5-248
H93
(I)
0.010 to 10.000 s
999: Manufacturer adjustment value
Y
Y1
Y2
999
H94
Cumulative run time of motor
1
0 to 99990 hours (updated in 10 hour units)
Change in cumulative motor run time (reset possible)
N
N
-
5-240
5-248
H95
DC braking
(Braking response mode)
0: Slow response
1: Quick response
Y
Y
1
5-102
5-248
H96
STOP key priority/
Start check function
0: STOP key priority disable/ Start check function disable
1: STOP key priority enable/ Start check function disable
2: STOP key priority disable/ Start check function enable
3: STOP key priority enable/ Start check function enable
Y
Y
0
5-249
H97
Clear alarm data
0: Disable
1: Clear alarm data (Automatically return to 0 after clearing data)
Y
N
0
5-249
H98
Protection/Maintenance
function
(Operation selection)
0 to 255 (Data is displayed in decimal)
0: Disable; 1: Enable)
Bit 0: Lower the carrier frequency automatically (0: Disable; 1: Enable)
Bit 1: Input phase loss protection (0: Disable; 1: Enable)
Bit 2: Output phase loss protection (0: Disable; 1: Enable)
Bit 3: DC link bus capacitor life judgment selection
(0: Factory default referenced; 1: User measurement value standard)
Bit 4: Judge the life of DC link bus capacitor (0: Disable; 1: Enable)
Bit 5: Detect DC fan lock (0: Enable; 1: Disable)
Bit 6: Braking transistor error detection (0: Disable; 1: Enable)
Bit 7: IP20/IP40 switching (0: IP20 ; 1: IP40)
Y
Y
*16
5-250
H99
Password function password
2
Setting/comparison
0000 to FFFF (in hexadecimal)
Y
N
0
5-252
*9: This is a function code for adjustment by the manufacturer. Do not access these function codes.
*15: When the sensorless vector control for PM is set to less than 10% of F04 (base frequency), the internal operation of H64 is limited to the P89
setting (%) of F04.
*16: Up to FRN0288G2S-2G/FRN0180G2-4G: 83 (decimal display) FRN0346G2S-2G/FRN0216G2-4G: 19 (decimal display)