5.2 Function Code Tables
5-24
Function
code
Name
Control method and Data setting range
Change when
running
Data copying
Factory
default
Related page
H101
Destination setting
0: Not selected
1: J
2: Asia
3: China
4: Europe
5: Americas
7󲷙 East Asia (Taiwan,etc.)
N
Y
1
5-255
H114
Anti-regenerative control
(Operation level)
0.0 to 50.0 %, 999 (Auto)
Y
Y
999
5-237
5-255
H116
Forced operation
(Operation selection)
0: [FMS] ON (Mode 1)
1: [FMS] ON/OFF torque method (Mode 1)
2: [FMS] ON latch method (Mode 1)
10: [FMS] ON (Mode 2)
11: [FMS] ON/OFF torque method (Mode 2)
12: [FMS] ON latch method (Mode 2)
20: [FMS] ON (Mode 3)
21: [FMS] ON/OFF torque method (Mode 3)
22: [FMS] ON latch method (Mode 3)
N
N
0
5-255
H117
(Confirmation time)
0.5 to 10.0s
Y
Y
3.0
H118
(Set frequency)
0.0 (Inherit): Based on normal set frequency such as F01
0.1 to 599.0 Hz
Y
Y
0.0
H119
(Operation direction)
0: Based on normal run command such as F02
2: Forward rotation
3: Reverse rotation
Y
N
0
H120
(Starting method)
0: Based on normal starting method
1: Auto search (Speed search)
Y
Y
0
H121
(Wait time)
0.5 to 20.0 s
Y
Y
5.0
H130
For special adjustment
(Torque limiting)
0.000 to 2.000; 999
Y
Y
999
5-257
H131
(Torque limiting)
0.000 ; 0.001 to 9.999 ; 999
Y
Y
999
H132
(Torque limiting)
0.000 ; 0.001 to 9.999 ; 999
Y
Y
999
H133
(Anti-regenerative control)
0.000 to 2.000; 999
Y
Y
999
5-257
H134
(Anti-regenerative control)
0.000 ; 0.001 to 9.999 ; 999
Y
Y
999
H135
(Anti-regenerative control)
0.000 ; 0.001 to 9.999 ; 999
Y
Y
999
H136
(Current limiting)
0.00 to 1.00; 999
Y
Y
999
5-257
H137
(Current limiting)
0.001 to 10.000; 999
Y
Y
999
H147
Speed control (JOG)
FF (Gain)
0.00 to 99.99 s
Y*
Y
0.00
5-257
5-300
H154
Torque bias (Mode selection)
0: Disable
1: Digital torque bias
2: Analog torque bias
3: RS-485 communications link (port 1)
4: RS-485 communications link (port 2)
5: Fieldbus link
N
Y
0
5-258
H155
(Level 1)
-300 to +300 %
Y
Y
0
H156
(Level 2)
-300 to +300 %
Y
Y
0
H157
(Level 3)
-300 to +300 %
Y
Y
0
H158
(Mechanical loss
compensation)
0 to 300 %
Y
Y
0
H159
(Startup timer)
0.00 to 1.00 s
N
Y
0.00
H161
(Shutdown timer)
0.00 to 1.00 s
N
Y
0.00
H162
(Limiter)
0 to 300 %
N
Y
200
H173
Magnetic flux level at light load
10 to 100 %
Y
Y
100
5-259
H180
Brake control signal
(Check-timer for brake
operation)
0.00 to 10.00 s
Y
Y
1.00
5-259
5-287
H190
Motor output phase sequence
selection
0: No phase sequence change
1: Terminal [U]: outputs U phase, terminal [V]: outputs W phase, terminal [W]:
outputs V phase
N
Y
0
5-260
H193
User preference dataset
(Save)
0: Disable
1: Save
N
N
0
5-216
H194
(Protection)
0: Save enable
1: Protected (Save disable)
Y
Y
0
H195
DC braking
(Braking timer at the startup)
0.00 (Disable): 0.01 to 30.00 s
is valid only when P30 = 0
Y
Y
0.00
5-102
5-260
H196
For adjustment by
manufacturer *9
0.001 to 9.999, 999
Y
Y
999
-