5.2 Function Code Tables
5-51
FUNCTION CODES
Chap 5
Function
code
Name
Control method and Data setting range
Change when running
Data copying
Factory
default
Related page
o40
to
Write function code
assignment 1
to
0000 to FFFF (in hexadecimal)
Data mapped I/O (Write)
The existence of support, and the number items supported differs depending
on the bus option type. Refer to the respective bus option instruction manuals
for details on the data setting method.
N
Y
0000
o47
Write function code
assignment 8
o48
to
Read function code
assignment 1
to
0000 to FFFF (in hexadecimal)
Data mapped I/O (Read)
The existence of support, and the number items supported differs depending
on the bus option type. Refer to the respective bus option instruction manuals
for details on the data setting method.
N
Y
0000
o59
Read function code
assignment 12
o60
Terminal [32]
(Function selection)
Same as E61
N
Y
0
o61
(Offset adjustment)
-5.0 to 5.0 %
Y*
Y
0.0
o62
(Gain adjustment)
0.00 to 400.00 %
Y*
Y
100.00
o63
(Filter setting)
0.00 to 5.00 s
Y
Y
0.05
o64
(Gain reference point)
0.00 to 100.00 %
Y*
Y
100.00
o65
(Polarity selection)
0: Bipolar
1: Unipolar
N
Y
1
o66
(Bias)
-200.0 to 200.00 %
Y*
Y
0.00
o67
(Bias reference point)
0.00 to 100.00 %
Y*
Y
0.00
o69
(Display unit)
Same as J105 (0 cannot be set.)
N
Y
2
o70
(Maximum scale)
-999.0 to 0.00 to 9990.0
N
Y
100.00
o71
(Minimum scale)
-999.0 to 0.00 to 9990.0
N
Y
0.00
o75
Terminal [C2]
(Range selection)
0: 4 to 20 mA Unipolar
1: 0 to 20 mA Unipolar
10: 4 to 20 mA Bipolar
11: 0 to 20 mA Bipolar
N
Y
0
o76
(Function selection)
Same as E61
N
Y
0
o77
(Offset adjustment)
-5.0 to 5.0 %
Y*
Y
0.0
o78
(Gain adjustment)
0.00 to 400.00 %
Y*
Y
100.00
o79
(Filter setting)
0.00 to 5.00 s
Y
Y
0.05
o81
(Gain reference point)
0.00 to 100.00 %
Y*
Y
100.00
o82
(Bias)
-200.0 to 200.00 %
Y*
Y
0.00
o83
(Bias reference point)
0.00 to 100.00 %
Y*
Y
0.00
o85
(Display unit)
Same as J105 (0 cannot be set.)
N
Y
2
o86
(Maximum scale)
-999.0 to 0.00 to 9990.0
N
Y
100.00
o87
(Minimum scale)
-999.0 to 0.00 to 9990.0
N
Y
0.00
o88
C1OFF signal
(Operation selection)
0: Signal ON following terminal [C1] wire break
1: Signal ON following terminal [C2] wire break
2: Signal ON following terminal [C1] or [C2] wire break
N
Y
2
o90
Terminal [Ao] / [CS2]
(Function selection)
Same as F31
Y
Y
0
o91
(Output gain)
0 to 300 %
Y*
Y
100
o93
Terminal [Ao]
(Polarity selection)
0: Bipolar
1: Unipolar
N
Y
1
o96
Terminal [CS] / ]CS1]
(Function selection)
Same as F31
Y
Y
0
o97
(Output gain)
0 to 300 %
Y*
Y
100
o101
to
Terminal [I1]
(Function selection)
to
See o101 to o116 in “Table 5.2.2 Control input terminal setting list table”.
N
Y
100
o116
Terminal [I16]
(Function selection)