5.3 Description of Function Codes 5.3.1 F codes (Fundamental functions)
5-112
Function selection (F31, F61)
F31 and F61 specify which data is monitored at output terminals [FM1] and [FM2]. An absolute value is output when
unipolar.
F31, F61
data
Subject of monitoring
Content
Definition of monitor amount
100 %
0
Output frequency 1
(before slip
compensation)
Output frequency of the inverter
(Equivalent to the motor
synchronous speed)
Maximum frequency 1 (F03)
Bipolar output possible at
reverse side minus
1
Output frequency 2
(after slip
compensation)
Output frequency of the inverter
Maximum frequency 1 (F03)
Bipolar output possible at
reverse side minus
2
Output current
Output current (RMS) of the inverter
Twice the inverter rated current
3
Output voltage
Output voltage (RMS) of the
inverter
200V series: 250 V
400V series: 500 V
4
Output torque
Motor shaft torque
Twice the rated motor load
Bipolar output possible
5
Load factor
Motor load factor
Twice the rated motor load
6
Power consumption
Input power of the inverter
Twice the rated output power
(Inverter rated output power
depending on F80)
7
PID feedback value
(PV)
Feedback value under PID control
100% of the feedback amount
8
PG feedback value
(speed)
Speed detected with the PG
interface, or estimated speed
(under speed sensorless vector
control)
Maximum speed as 100%
Bipolar output possible at
reverse side minus
9
DC link bus voltage
DC link bus voltage of the inverter
200V series: 500 V
400V series: 1000 V
10
Universal AO
Command from communication
( See “RS-485 Communication
User's Manual”)
±20,000
Bipolar output possible
11
Calibration (-)
For analog meter (bipolar)
calibration
Minus full scale output
Always full scale (-10 V) output
13
Motor output
Motor output (kW)
Twice the rated motor output
(P02/A16 setting value)
14
Calibration (+)
For meter calibration
Full scale output
Always full scale (equivalent to
100%) output
15
PID command (SV)
Command value under PID control
PID command 100 %
16
PID output (MV)
Output level of the PID processor
under PID control (Frequency
command)
Maximum output frequency
(F03)
Bipolar output possible
17
Master-follower angle
deviation
Position deviation when performing
master-follower operation
0% to 50% to 100%,
representing a deviation of
-180° to 0° to +180° respectively
18
Inverter heat sink
temperature
Heat sink detection temperature of
inverter
200 °C