EasyManua.ls Logo

Fuji Electric FRENIC MEGA G2 Series - Page 361

Fuji Electric FRENIC MEGA G2 Series
970 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.3 Description of Function Codes 5.3.2 E codes (Extension terminal functions)
5-177
FUNCTION CODES
Chap 5
FUNCTION
CODES
F Codes
E Codes
C Codes
P Codes
H Codes
A Codes
b Codes
r Codes
J Codes
d Codes
U Codes
y Codes
K Codes
E42
LED display filter
Excluding speed monitor (when E43 = 0), E42 specifies a filter time constant to be applied for displaying the output
frequency, output current and other running status monitored on the LED monitor on the keypad. If the display varies
unstably so as to be hard to read due to load fluctuation or other causes, increase this filter time constant.
Data setting range: 0.0 to 5.0 (s)
E43
LED monitor (Item selection)
Related function code: E48 LED monitor (speed monitor item)
Selects the operating state monitor information displayed on the keypad LED.
Specifying the speed monitor with E43 provides a choice of speed-monitoring formats selectable with E48 (LED
monitor).
Monitor item
Monitor
example
LED indication
Unit
Meaning of displayed value
E43 data
Speed monitor
Function code E48 specifies what to be displayed on the LED monitor and LED
indicators.
0
Output frequency 1
(before slip
compensation)
50.00
HzAkW
Hz
Indicated value = Output frequency (Hz)
(E48 = 0)
Output frequency 2
(after slip
compensation)
50.00
HzAkW
Hz
Indicated value = Output frequency (Hz)
(E48 = 1)
Reference
frequency
50.00
HzAkW
Hz
Indicated value = Reference frequency
(Hz)
(E48 = 2)
Motor rotation speed
1500
HzAkW
min-1
P01(A15)
120
Hz)󱽓󱘈󲷜󰻝󰧹
(E48 = 3)
Load rotation speed
300.0
HzAkW
min-1
Indicated value = Output frequency (Hz) x
E50/E39
Note
(E48 = 4)
Feed speed
300.0
HzAkW
m/min
Indicated value = Output frequency (Hz) x
E50/E39
Note
(E48 = 5)
Transport time for
specified length
50.00
HzAkW
min
Indicated value = E50
Note
/(Output
frequency x E39)
(E48 = 6)
Speed (%)
50.0
HzAkW
%
100
1))󰻝󰧹󰬒󲥸
󰻝󰧹
󱽓󱘈󲷜
出力
(E48 = 7)
Line speed set value
1800.
HzAkW
m/min
Line speed setting value after calculating
acceleration/deceleration with d168 and
d169 for feed speed set with E48 = 5
(E48 = 8)
Line speed output
value
1800.
HzAkW
m/min
Roll frequency setting value compensated
with winding diameter calculation result for
line speed set with E48 = 8
(E48 = 9)
Output current
12.34
HzAkW
A
Current output from the inverter in RMS
3
Output voltage
200U
HzAkW
V
Output voltage (RMS) of the inverter
4
Calculated motor output
torque
50
HzAkW
%
Motor output torque in % (Calculated
value)
8
Power consumption
10.25
HzAkW
kW
Input power to the inverter
9
PID process command
10.00.
HzAkW
-
PID command and its feedback converted
into physical quantities of the object to be
controlled (e.g. temperature)
10
PID feedback value
9.00.
HzAkW
-
12
Timer value
100
HzAkW
s
Timer value (remaining run time)
13
PID output
100.0.
HzAkW
%
PID output indicated with percentage (%)
with maximum output frequency (F03,
A01) being 100%
14
Load factor
50;
HzAkW
%
Load factor of motor indicated with
percentage (%) with rated output being
100%
15
Motor output
9.85
HzAkW
kW
Motor output (kW)
16
Indicated
value
=
Output frequency
Maximum output frequency (F03 (A01))
100
Indicated value = Output frequency (Hz)

Table of Contents