5.3 Description of Function Codes 5.3.2 E codes (Extension terminal functions)
5-178
Monitor item
Monitor
example
LED indication
Unit
Meaning of displayed value
E43 data
Analog signal input
monitor
82.00
HzAkW
-
An analog input to the inverter in a format
suitable for a desired scale.
17
Current position pulse
1234
HzAkW
Pulse
Current position pulse
21
Positioning deviation pulse
2345
HzAkW
Pulse
Command current position and feedback
current position deviation indicated with
user value
22
Torque current
48
HzAkW
%
Torque current command value or
calculated torque current
23
Flux command value
50
HzAkW
%
Magnetic flux command value
(Available only under vector control)
24
Integral power
consumption
100.0
HzAkW
kWh
100
(kWh) hour- wattInput
value Indicated =
25
Winding diameter
1234
HzAkW
mm
Winding diameter calculation result display
for constant surface speed control
26
Position control start
position
1234
HzAkW
-
Position when run command turns ON or
“POS-SET” command turns ON indicated
with user value
27
Stop target position
2345
HzAkW
-
Stop target position indicated with user
value
28
PID deviation
1.00.
HzAkW
-
PID command value and PID feedback
value deviation converted into physical
quantities of the object to be controlled
29
Torque bias
25
HzAkW
%
Torque bias value display
30
Estimated inertia
acceleration/
deceleration time
conversion value
1.234
HzAkW
s
Display of estimated inertia result in logic
acceleration/deceleration time
See function code P24.
31
Customizable logic output
82.00
HzAkW
-
Display of output content for specific
customizable logic step
See function codes U98, U99.
32
ON, OFF
Note: The function code applied when the motor changes will also change.