5.3 Description of Function Codes 5.3.2 E codes (Extension terminal functions) 
 
 
Electric energy pulse output unit setting   
 
 
By setting “POUT” integral power consumption pulse output to the digital output terminals with E20 to E24, or E27, 
a 0.15 s pulse can be output each time the integral power consumption increase reaches the unit amount selected 
with this function code. Accuracy is not so good, and therefore this cannot be used as data for making business 
deals. 
 
Integral power consumption pulse output unit amount 
 
時刻
0
積算電力
パルス出力
POUT
時刻
ON
ON
ON
OFF
OFF
OFF
OFF
ON幅:0.15s
E57設定値で
選択される
単位量
積算電力
 
Fig. 5.3-24 
( Function codes E20, E24 and E27, data = 126) 
 
 
Terminal [12], [C1] (C1 function), [V2], [C1] (V3 function) (extension function 
selection)
 
 
If other than a frequency setting signal is assigned to analog input terminals, change this function code. The same 
function cannot be set for another terminal. 
 
Auxiliary frequency 
setting 1 
Auxiliary frequency input to be added to the reference frequency given 
by frequency setting 1 (F01). Will not be added to any other reference 
frequency given by frequency setting 2 and multistep frequency 
commands, etc. 
100 %/full scale. 
Effective range: -100% to 100% 
Auxiliary frequency 
setting 2 
Auxiliary frequency input to be added to all frequency commands. Will 
be added to frequency command 1, frequency command 2, multistep 
frequency commands, etc. 
100 %/full scale. 
Effective range: -100% to 100% 
Inputs command sources such as temperature and pressure under PID 
control. You also need to set function code J02. 
100 %/full scale. 
Effective range: -100% to 100% 
Unit amount selected 
with E57 setting value 
Integral  power  pulse 
output POUT