5.3 Description of Function Codes 5.3.2 E codes (Extension terminal functions)
Inputs feedback values such as temperature and pressure under PID
control.
100 %/full scale.
Effective range: -110% to 110%
Multiplies the final frequency command value by this value, for use in
the constant line speed control by calculating the winder diameter or in
ratio operation with multiple inverters.
100 %/full scale.
Effective range: -200% to 200%
Used when analog inputs are used as torque limiters.
( Function code F40)
200 %/full scale.
Effective range: -400% to 400%
Used when analog inputs are used as torque limiters.
( Function code F40)
200 %/full scale.
Effective range: -400% to 400%
Used when analog inputs are used as torque bias.
( Function code H154)
200 %/full scale.
Effective range: -400% to 400%
Analog inputs to be used as torque commands under torque control.
( Function code H18)
Effective range: -400% to 400%
Analog inputs to be used as torque current commands under torque
control. ( Function code H18)
Effective range: -400% to 400%
Acceleration/decele
ration time ratio
setting
Multiplies the ratio based on the analog input amount by the
acceleration/deceleration time.
( Function code F07)
Effective range: -400% to 400%
The frequency obtained by multiplying the maximum frequency by the
analog input amount is used as the upper limit frequency.
( Function code F15)
Effective range: 0% to 100%
The frequency obtained by multiplying the maximum frequency by the
analog input amount is used as the lower limit frequency.
( Function code F15)
Effective range: 0% to 100%
Auxiliary frequency
setting 3
This is added immediately after adding auxiliary frequency setting 1.
100%/full scale (see block diagram)
Effective range: -100% to 100%
Auxiliary frequency
setting 4
This is added immediately after adding auxiliary frequency setting 2.
100%/full scale (see block diagram)
Effective range: -100% to 100%