5.3 Description of Function Codes 5.3.3 C codes (Control functions)
Multistep Frequency 1 to 15
These function codes specify 15 frequencies required for driving the motor at frequencies 1 to 15.
Turning terminal commands “SS1”, “SS2”, “SS4” and “SS8” ON/OFF selectively switches the reference frequency
of the inverter in 15 steps. To use this features, you need to assign “SS1”, “SS2”, “SS4” and “SS8” (“Select multistep
frequency”) to the digital input terminals with E01 to E09 (data = 0, 1, 2, and 3).
Multistep frequency 1 to 15 (C05 through C19)
• Data setting range: 0.00 to 599.0 (Hz)
The combination of “SS1”, “SS2”, “SS4” and “SS8” and the selected frequencies is as follows.
Other than multistep frequency*
C05 (Multistep frequency 1)
C06 (Multistep frequency 2)
C07 (Multistep frequency 3)
C08 (Multistep frequency 4)
C09 (Multistep frequency 5)
C10 (Multistep frequency 6)
C11 (Multistep frequency 7)
C12 (Multistep frequency 8)
C13 (Multistep frequency 9)
C14 (Multistep frequency 10)
C15 (Multistep frequency 11)
C16 (Multistep frequency 12)
C17 (Multistep frequency 13)
C18 (Multistep frequency 14)
C19 (Multistep frequency 15)
* “Other than multistep frequency” includes frequency setting 1 (F01), frequency setting 2 (C30) and other
frequency command sources except multistep frequency commands.