EasyManua.ls Logo

Fuji Electric FRENIC MEGA G2 Series - Page 403

Fuji Electric FRENIC MEGA G2 Series
970 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.3 Description of Function Codes 5.3.5 H codes (High performance functions)
5-219
FUNCTION CODES
Chap 5
FUNCTION
CODES
F Codes
E Codes
C Codes
P Codes
H Codes
A Codes
b Codes
r Codes
J Codes
d Codes
U Codes
y Codes
K Codes
H09, d67
Starting characteristic (Auto search mode)
Related function codes: H49 (Starting mode, auto search delay time 1)
H46 (Starting mode, auto search delay time 2)
Specify the mode for auto search without stopping the idling motor. The mode can be specified for each restart after
momentary power failure and each start of normal operation. The starting mode can be switched by assigning “STM”
to a general-purpose digital input signal. If it is not assigned, “STM” is regarded to be OFF. (Data = 26)
H09/d67 (Starting mode, auto search) and terminal command “STM” (“Enable auto search for idling
motor speed at starting”)
The combination of starting characteristics H09 and d67 data and the “STM” signal determines whether to perform
the auto search when starting.
Function code
Drive control
Factory default
H09
V/f control (F42 = 0 to 2)
0: Disable
d67
Sensorless vector control (F42 = 5, 15)
1: Enable (Only at restart
after momentary power
failure)
H09/d67 data
Starting characteristic
selection “STM”
Starting characteristic
Restart mode after momentary
power failure (F14 = 3 to 5)
For normal startup
0: Disable
OFF
Auto search disable
Auto search disable
1: Enable
OFF
Auto search enable
Auto search disable
2: Enable
OFF
Auto search enable
Auto search enable
-
ON
Auto search enable
Auto search enable
When “STM” is ON, auto search for idling motor speed at starting is enabled regardless of the H09 setting.
( Function codes E01 to E09 data = 26)
By setting 15 for F42, it is automatically set to 2: This is set to enable (At normal start and at restart after momentary
power failure).
Auto search for idling motor speed to follow
Starting the inverter (with a run command ON, BX OFF, auto-reset, etc.) with STM being ON searches for the idling
motor speed for a maximum of 1.2 seconds to run the idling motor without stopping it. After completion of the auto
search, the inverter accelerates the motor up to the reference frequency according to the frequency command and
the preset acceleration time.
Frequency command
Motor speed
Motor speed
estimation
“STM”
“FWD”
Starting
mode (auto
search delay
time 1)
(H49)
1.2 s max.

Table of Contents