(1) Various signals (coast to stop command, external alarm, multi-speed selection, etc.) can
be set with function codes E01 to E09, E98, E99. Refer to Chapter 5 "FUNCTION
CODES" for details.
(2) The input mode and SINK/SOURCE can be switched using SW1. (See 2.2.7 Switching
switches.)
(3) The operating mode between each digital input terminal and terminal [CM] can be
switched to "ON when shorted (active ON)" or "OFF when shorted (active OFF)".
(4) Digital input terminals [X6] and [X7] can be set up as a pulse train input terminal by
changing the function code
Maximum wire length: 20 m
Maximum input pulse
30 kHz: When connected to open collector output pulse generator
(A pull-up resistor and pull-down resistor are required. Refer to ■When inputting pulse
train with terminals [X6] and [X7].
100 kHz: When connected to complementary output pulse generator
Refer to Chapter 5 "FUNCTION CODES" for details on function code settings.
<Digital input circuit specifications>
(1) When terminals [EN1]-[PLC] or terminals [EN2]-[PLC] are OFF, the inverter output
transistors stop switching (safe torque off: STO).
Be sure to operate terminals [EN1] and [EN2] simultaneously; otherwise an ecf alarm is
issued and the operation of the inverter will be disabled.
(2) The input mode for terminals [EN1] and [EN2] is fixed to source. The mode cannot be
switched to sink.
(3) This function can be enabled and disabled with SW7. If using this function, set the
respective SW7 switches to the OFF side.
<Terminal [EN1], [EN2] circuit specifications>