11.17 IP40 Compatibility Attachment (P40ST-F□1)
11-81
SELECTING PERIPHERAL EQUIPMENT
Changes to the specifications from standard specification 1 (basic type) when this compatibility attachment is
installed are as follows. Other specifications are the same as the standard specification 1 (basic type).
Rated output current
The rated output current in the case of HND (High, Normal Duty applications) for three-phase 200V series low duty
applications is shown in the following table.
Table 11.17-4
Applicable inverter type (FRN□□□G2S-2)
Ambient temperature
-10 to +40 °C
Number of installable option cards (PCBs)
By installing this compatibility attachment, a single option card can be installed.
(Two OPC-RY relay output interface cards can be installed.)
All option cards are supported.
The connection port differs based on the specifications for each option.
(4) Setting change
Select IP40 with function code H98 (Protection/Maintenance function (Mode selection)) bit 7 (IP20/IP40 switching).
It is necessary to change to a level of protection appropriate for IP40 due to the protective coordination relationship.