11.22 Built-in Option Card Types and Ports in Which They Can be Installed
11-123
SELECTING PERIPHERAL EQUIPMENT
11.22.12 PG Interface Card (OPC-PG)
The PG interface card is equipped with a 2 system pulse (ABZ-phase) input circuit and PG (pulse generator) power
supply output circuit, and the following functions can be realized by installing it in FRENIC-MEGA.
(1) Speed control with PG feedback signal (vector control with speed sensor, V/f control with speed sensor, dynamic
torque vector control with speed sensor) and servo lock function
(2) Pulse train input as frequency command
Note) By installing this interface card in FRENIC-MEGA, the inverter unit terminal [X6] and [X7] pulse train input
function cannot be used.
Applicable port
This interface card can be installed only in port C of the three FRENIC-MEGA option connection ports (A, B, and C
ports).
PG interface specifications
The PG interface specifications for this interface card are shown in Table 11.22-42.
Table 11.22-42 PG interface specifications
20 to 3000 P/R (A-phase, B-phase, Z-phase incremental type)
Open collector method (wire length: 20 m or less)
Complementary method (wire length: 100 m or less)
High level ≥ 8 V, Low level ≤ 3 V
(when using 12 V power supply specification)
High level ≥ 10 V, Low level ≤ 3 V
(when using 15 V power supply specification)
+12 VDC ±10%/120 mA or less, or +15 VDC ±10%/120 mA or less
*1 If the PG power supply current exceeds 120 mA, use an external power supply.
Pulse train input interface specifications
The pulse train input specifications for this interface card are shown in Table 11.22-43.
Table 11.22-43 Pulse train input interface specifications
Up to 30 kHz (open collector method)
Up to 100 kHz (complementary method)
Open collector method (wire length: 20 m or less)
Complementary method (wire length: 100 m or less)
High level ≥ 8 V, w level ≤ 3 V
(when using 12 V power supply specification)
High level ≥ 10 V, w level ≤ 3 V
(when using 15 V power supply specification)