Appendix G Conformity with Standards
Appendix-33
APPENDICES
Leakage current of EMC-filter built-in type of inverters
An EMC filter uses grounding capacitors for noise suppression which increase leakage current. The use of
grounding capacitors leads to an increase in leakage current, and therefore a check should be carried out to ensure
that the power supply system has not been affected.
As the touch current (leakage current) of inverters with EMC-filter is relatively high, it is of essential importance to
always assure a reliable connection to Protective Earth (PE). (Current values are shown in Table G.1-3.)
In Table G.1-3, for the inverter types whose leakage currents are equal to or exceed the critical value of 3.5 mA
AC or 10 mA DC (IEC 61800-5-1), the minimum cross sectional area of the PE-conductor should be:
• 10 mm
2
(Cu-conductors)
• 16 mm
2
(Al-conductors)
Failure to observe this could result in electric shock.
Table G.1-3 Leakage current of EMC filter built-in type of inverters
Power system
Inverter type
Leakage current (mA)
Three-phase 400 V *1)
FRN0002G2E-4G
3
FRN0003G2E-4G
FRN0004G2E-4G
FRN0006G2E-4G
FRN0009G2E-4G
FRN0018G2E-4G
7
FRN0023G2E-4G
FRN0031G2E-4G
FRN0038G2E-4G
5
FRN0045G2E-4G
FRN0060G2E-4G
FRN0075G2E-4G
11
FRN0091G2E-4G
FRN0112G2E-4G
FRN0150G2E-4G
5
FRN0180G2E-4G
FRN0216G2E-4G
FRN0260G2E-4G
FRN0325G2E-4G
FRN0377G2E-4G
FRN0432G2E-4G
FRN0520G2E-4G
FRN0650G2E-4G
FRN0740G2E-4G
FRN0960G2E-4G
FRN1040G2E-4G
FRN1170G2E-4G
FRN1386G2E-4G
*1) Calculated based on these measuring conditions: 480 V/60 Hz, neutral grounding,
interphase voltage unbalance ratio of 2%.