Appendix G Conformity with Standards
Appendix-43
G.2 Harmonic Component Regulations in EU
[ 1 ] General comments
When you use general-purpose industrial inverters in the EU, the harmonics emitted from the inverter to power lines
are strictly regulated as stated below.
If an inverter whose rated input is 1 kW or less is connected to public low-voltage power supply, it is regulated by
the harmonics emission regulations from inverters to power lines (with the exception of industrial low-voltage power
lines). (Refer to Fig. G.2-1.)
Fig. G.2-1 Power supply system
[ 2 ] Compliance with the harmonic component regulation
Table G.2-1 Compliance with harmonic component regulations
Applicable
DC reactor type
Y: Meets EN61000-3-2 (+A14) standard, and therefore the product may be connected to a commercial voltage
power supply.
N: Does not meet EN61000-3-2 (+A14) standard. If connecting the product to a commercial low voltage power
supply, it will be necessary to obtain the permission of the local power company. When harmonic current data is
necessary, consult your Fuji Electric representative.
*1: The □ in the inverter type is replaced by a letter of the alphabet indicating the type.
*2: Evaluated by the level of harmonics flow to the 400 VAC line when three-phase 200 VAC power is supplied from
the three-phase 400 VAC power via a step-down transformer.