3.3 Running Mode
3-14
3.3.7 Jogging operation
This section provides the procedure for jogging the motor.
(1) Make the inverter ready to jog by following the steps below. The LED monitor should display JoG.
∙ Set the operation mode to Running mode. (See “3.2 Overview of Operation Modes”.)
∙ Press the + keys simultaneously. The LED monitor displays the jogging frequency for approximately
one second and then displays
joG
again.
• Function codes C20, H54 and H55 specify the jogging frequency and acceleration/deceleration time,
respectively. Use these function codes exclusively for the jogging operation with your needs.
• Alternatively, using the input terminal command JOG (“Ready for jogging”) switches between the
normal operation state and ready-to-jog state.
• Switching between the normal operation state and read-to-jog state with the +
keys is
possible only when the inverter is stopped.
(2) Jogging the motor.
∙ Hold down the keypad key during which the motor continues jogging. To decelerate to stop the motor,
release the key.
(3) Exiting the ready-to-jog state and returning to the normal operation state.
Press the + keys simultaneously.
Refer to function codes E01 to E09 in Chapter 5 “5.3.2 E codes (terminal functions)” for details.