Another possible situation where the timer hold facility may be used to reduce fault clearance times is 
for intermittent faults. An example of this may occur in a plastic insulated cable. In this application it is 
possible for the fault energy to melt and reseal the cable insulation, thereby extinguishing the fault. 
This process repeats to give a succession of fault current pulses, each of increasing duration with 
reducing intervals between the pulses, until the fault becomes permanent.  
When the reset time is instantaneous, the device will repeatedly reset and not be able to trip until the 
fault becomes permanent. By using the Timer Hold facility the device will integrate the fault current 
pulses, thereby reducing fault clearance time.  
The timer hold facility is available to all three stages of OC and EF functions.  
The Definite Time Reset characteristic is applicable for IEC curves / DT.  
The value of the Reset Timer depends on the type of the timer associated to the pick-up phase (Earth) 
threshold. 
Type of timer associated with phase (earth) 
threshold 
Reset Timer 
    DT Reset Characteristic  IDMT Reset Characteristic 
- For DT time delay  0 – 100s  Not available 
- For IDMT IEC time delay  0 – 100s  Not available 
- For IDMT IEEE or CO time delay 
 (0.025-1.2) 
 
The mathematical formula applicable to the five curves is: 
t =         RTMS x K    
 --------------------  
 1- (I / Is) 
α 
 
Where: 
 
t      =  Reset time 
K    =   Factor (see table) 
I      =  Value of the measured current 
Is    =  Value of the programmed threshold (pick-up value)  
α   =  Factor (see table) 
RTMS  Reset time multiplier (RTMS) setting is between 0.025 and 1.2 
 
Description  Standard  K  α 
Moderate Inverse   IEEE  4.85  2 
Very Inverse   IEEE  21.6  2 
Extremely Inverse  IEEE  29.1  2 
US Inverse  CO8  5.95  2 
2.2  Phase Overcurrent Protection 
Phase current faults are faults where fault current flows between two or more phases of a three-phase 
power system. The fault current may be between the phase conductors only or, between two or more 
phase conductors and earth. There are three types of phase fault: 
•  Line to Line (accounting for approximately 8% of all faults)