2nd Harm Thresh 
20% 
By using the (5) or (6) key, the desired 2ndHarm Thresh can be set. 
The setting range is 5% to 70% in steps of 1%.  
I>lift 2H 
10.00 A 
Editable setting 
By using the (5) or (6) key, the desired I>lift 2H setting can be done. 
The setting range is 4.00 to 32.00 In in steps of 0.01 In. 
2.3.16.3  Group1 –Overcurrent Submenu 
2.3.16.3.1 
Edit Settings
 (if I>1 Function, I>2 Function and I>3 Function are disabled) 
GROUP 1 
 
Password protected window for “GROUP 1’’ settings: 
 SYSTEM CONFIG, OVERCURRENT, NEG SEQUENCE O/C, BROKEN 
CONDUCTOR, EARTH FAULT 1, EARTH FAULT 2, THERMAL 
OVERLOAD, COLD LOAD PICKUP, UNDERCURRENT and CB FAIL. 
Note: Group 1 Setting will be seen only when it is enabled in 
Configuration setting. 
OVERCURRENT 
 
Password protected window for Overcurrent i.e. I>1 Function, I>2 
Function and I>3 Function setting to Disabled / DT/ IEC S Inverse/ S 
Inverse (1.3Sec)/ IEC V Inverse/ IEC E Inverse/ UK LT Inverse /IEEE M 
Inverse/ IEEE V Inverse/ IEEE E Inverse /US Inverse /US ST Inverse 
I>1Function 
Disabled 
By using the (5) or (6) key, I>1Function can be Disabled  
 
I>2Function 
Disabled 
Editable setting 
By using the (5) or (6) key, I>2Function can be Disabled  
 
I>3Function 
Disabled 
Editable setting 
By using the (5) or (6) key, I>3Function can be Disabled  
 
2.3.16.3.2 
Edit Settings
 (if I>1 Function is selected for IEC curve) 
GROUP 1 
 
Password protected window for “GROUP 1’’ setting: 
SYSTEM CONFIG, OVERCURRENT, NEG SEQUENCE O/C, BROKEN 
CONDUCTOR, EARTH FAULT 1, EARTH FAULT 2, THERMAL 
OVERLOAD, COLD LOAD PICKUP, UNDERCURRENT and CB FAIL. 
Note: Group 1 Setting will be seen only when it is enabled in 
Configuration setting. 
OVERCURRENT 
 
Password protected window for Overcurrent i.e. I>1 Function, I>2 
Function and I>3 Function setting to Disabled / DT/ IEC S Inverse/ S 
Inverse (1.3Sec)/ IEC V Inverse/ IEC E Inverse/ UK LT Inverse /IEEE M 
Inverse/ IEEE V Inverse/ IEEE E Inverse /US Inverse /US ST Inverse