disturbance records locally via the front panel LCD. This waveform can be downloaded via the 
communication port for further analysis.  
The fault recording is set by Trigger Position cell. The Trigger Position cell sets the trigger point as 
a percentage of the duration.  
The details of the disturbance record are as follows: 
Capacity:       5 records of 1 sec each  
Pre fault Trigger position:   Programmable 
Sampling rate:      16 samples / cycles  
Triggers:       Trip signals, external trigger via opto input assignment. 
Data:        5 analogue channels and up to 33 digital channels (physical and logical 
        status).  
2.2  Record Control 
The data stored in Event/Fault/Maintenance/Disturbance Records can be cleared by enabling the 
settings Clear Events/Clear Faults/Clear Maint/Clear Dist Recs in Record Control menu. The 
Thermal State can be reset by enabling the Thermal Reset setting. 
2.3  Display of Measuring Parameters 
The device directly measures and calculates a number of system quantities, which are updated at 
regular intervals. These values can be viewed in the MEASUREMENTS menu on the LCD screen 
using the navigation keys on the front panel or using the P50 Agile configurator tool. 
In normal conditions the relay displays Primary and Secondary current value of phases A, B, C and 
earth current N as per phase/earth CT ratio within ±2% accuracy and Thermal state in %.  
The device measures and displays the following quantities: 
Parameter  Unit  Description 
IA  amp  Primary current in phase A 
IB  amp  Primary current in phase B 
IC  amp  Primary current in phase C 
Primary earth current (measured) 
Primary earth current (derived) 
ia  amp  Secondary current in phase A 
ib  amp  Secondary current in phase B 
ic  amp  Secondary current in phase C 
in1  amp  Secondary earth current (measured) 
Secondary earth current (derived) 
Secondary -ve phase sequence current 
i1  amp  Secondary +ve phase sequence current 
I2/I1  %  Ratio of I2/I1 
TC  count 
Breaker Trip counter 
(Count of number of trips issued by relay) 
BOC  count 
Breaker operation counter  
(Count of total breaker operations- 
local & relay tripping ) 
BOT   millisecond 
(Breaker contact opening time for the latest 
trip)