The MCU acquires analog values @ 16 samples per cycle. Digital signal processing (DSP) performs 
powerful Numerical algorithms which convert this signal in to equivalent vectors. Once the signal is 
converted into vectors, number of parameters are derived from it such as phase currents (Ia, Ib, Ic), 
positive sequence current (I1) and negative sequence current (I2). The MCU also calculates 2
nd
 
harmonic content of the current signals which is utilised for detection of inrush currents. All 
measurements are tuned to fundamental frequency i.e. 50 Hz or 60 Hz, so that relay will remain stable 
during distorted waveform generated by modern electronics load.  
The typical Frequency response of tuned filter for 50 Hz is as shown in figure 4. 
 
Figure 4: Frequency response of tuned filter for 50 Hz 
The measurement is totally immune to all higher harmonics which makes relay operation absolute 
reliable.  All these measured values are then used for different protection functions such as over 
current/Earth Fault and Negative phase sequences. The actual protection function depends on type of 
relay and described in the rest of the document.     
2.4  Digital input /output module 
This module supports 4 numbers of Digital input DI and 4 numbers of Digital output DO channels for 
acquiring filed signals or controlling field devices respectively. The DIs are isolated from other circuits 
by using Opto isolators. The threshold voltage at which Opto coupler turns ON is controlled by 
comparator based on the voltage range selected during device ordering.  
2.5  Power supply module 
The Power supply module is a designed using modern PWM based switching mode technique. It 
converts input supply to the 12 V and 24 Vdc low voltage supply for relay electronics and control 
circuit. It also provides necessary isolation from input power supply. The Normal operating voltage 
range is 24V - 50V DC or 110V – 230 VAC/DC.  
2.6  Communication module 
P153 supports 2 numbers of isolated ports for communication.  
•  USB port provided on front of the relay 
•  RS485 (2 wire) port provided on the rear side of relay. 
The relay can be accessed using the P50 Agile Configurator. Rear port supports open protocols like 
IEC60870-5-103/MODBUS and is used for external communication.