Note 1:  Terminal blocks must not be detached whilst any current transformer (CT) circuit is live. CT shorting 
must be achieved by external means; the product does not include this facility. 
Note 2:  For 5A CT secondary, we recommend using 2 x 2.5 mm
2
 PVC insulated multi-stranded copper wire. 
2.3.3.7  EIA(RS) 485  Connections 
For connecting the EIA (RS485), use 2-core screened cable with a maximum total length of 1000 m or 
200 nF total cable capacitance. 
A typical cable specification would be: 
•  Each core: 16/0.2 mm
2
 copper conductors, PVC insulated 
•  Nominal conductor area: 0.5 mm
2
 per core 
•  Screen: Overall braid, PVC sheathed 
There is no electrical connection of the cable screen to the device. The link is provided purely to link 
together the two cable screens. 
2.3.3.8  Output Relay Connections 
These should be wired with 1 mm PVC insulated multi-stranded copper wire terminated with M4 ring 
terminals. 
2.3.3.9  USB Connection 
The IED has a type B USB socket on the front panel. A standard USB printer cable (type A one end, 
type B the other end) can be used to connect a local PC to the IED. This cable is the same as that 
used for connecting a printer to a PC.