EasyManuals Logo

GE Agile P153 User Manual

GE Agile P153
268 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #17 background imageLoading...
Page #17 background image
P50 Agile P153 Chapter 2 - Safety Information
P153/EN M/A
2-7
Warning:
The PCT is sometimes used to terminate cable screens. Always check the
PCT’s integrity after adding or removing such earth connections.
Warning:
Use a locknut or similar mechanism to ensure the integrity of
stud-connected PCTs.
Caution:
The recommended minimum PCT wire size is 2.5 mm² for countries whose
mains supply is 230 V (e.g. Europe) and 3.3 mm² for countries whose mains
supply is 110 V (e.g. North America). This may be superseded by local or
country wiring regulations.
For P60 products, the recommended minimum PCT wire size is 6 mm². See
product documentation for details.
Caution:
The PCT connection must have low-inductance and be as short as possible.
Caution:
All connections to the equipment must have a defined potential.
Connections that are pre-wired, but not used, should be earthed, or
connected to a common grouped potential.
3.6 PRE-ENERGISATION CHECKLIST
Caution:
Check voltage rating/polarity (rating label/equipment documentation).
Caution:
Check CT circuit rating (rating label) and integrity of connections.
Caution:
Check protective fuse or miniature circuit breaker (MCB) rating.