7 Protection Parameter Settings 
 
 
4.  E/F CT Primary  100A  1 to 30000A step 1A 
This setting determines the earth current transformer input primary current rating. 
This setting determines the earth current transformer input secondary current rating. 
2.6  RECORD CONTROL Settings 
1.  Password  0000  0000 to zzzz 
This setting specifies to enter the set password 
Selecting “Yes” will erase the existing events stored in the relay. 
3.  Clear Faults  No  Yes / No 
Selecting “Yes” will erase the existing fault records from the relay. 
4.  Clear Dist Recs  No  Yes / No 
Selecting “Yes” will erase the existing disturbance records from the relay. 
Selecting “Yes” will erase the existing maintenance records from the relay. 
6.  Thermal Reset  No  Yes / No 
Selecting “Yes” will reset the existing thermal state to zero. 
2.7  COMMUNICATION Settings 
Sr. No  Parameter  Defaults setting  Setting / Ranges 
This setting specifies to enter the set password 
2.  RP1 Address  1  1 to 247 step 1 
This setting sets the address of RP1. 
9600 / 19200 / 38400 / 57600 
This cell sets the communication speed between relay and master station. It is important that both relay and master station are set at the 
same speed setting. 
This cell sets the parity format used in the data frames. It is important that both relay and master station are set with the same parity 
setting. 
This setting enables or disables time synchronization with master clock 
2.8  IO CONFIGURATION Settings 
Sr. No  Parameter  Defaults setting  Setting / Ranges 
1.  Password  0000  0000 to zzzz 
This setting specifies to enter the set password 
2. 
Gen Strt* 
0000 
1 = assigned ; 0 = not assigned 
This cell sets the output contact RL1 – RL6 for desired function. 
3. 
 Gen Strt* 
00 
1 = assigned ; 0 = not assigned