2.3.16.9.2 
Edit Settings
 (If I>1 Function selected for IEC curve) 
GROUP 1 
 
Password protected window for “GROUP 1’’ settings:  
SYSTEM CONFIG, OVERCURRENT, NEG SEQUENCE O/C, BROKEN 
CONDUCTOR, EARTH FAULT 1, EARTH FAULT 2, THERMAL 
OVERLOAD, COLD LOAD PICKUP, UNDERCURRENT and CB FAIL. 
Note: Group 1 Setting will be seen only when it is enabled and set as 
Active Group in Configuration setting. 
COLD LOAD PKP 
 
Password protected window for 
i.e. tcold Time Delay, 
tclp Time Delay, I>1 Status, I>2 Status, I>3 Status, IN1>1 Status, IN1>2 
Status, IN1>3 Status, IN2>1 Status, IN2>2 Status and IN2>3 Status. 
tcold Time Delay 
7200 S 
Editable setting 
By using the (5) or (6) key, tcold Time Delay can be set. The setting 
range is from 0 to 14400s in steps of 1s.  
tclp Time Delay 
7200 S 
Editable setting 
By using the (5) or (6) key, tclp Time Delay can be set. The setting 
range is from 0 to 14400 in steps of 1.  
I>1 Status    
Enabled 
By using the (5) or (6) key, desired I>1 Status is Enabled. 
I>1 Current Set  
1.50 A  
Editable setting 
By using the (5) or (6) key, I>1 Current Set can be set. The setting 
range is from 0.05 to 4.00 In in steps of 0.01 In.  
I>1 TMS  
1.1 
Editable setting 
By using the (5) or (6) key, I>1 TMS can be set. The setting range is 
from 0.025 to 1.2 in steps of 0.005