7 Protection Parameter Settings  
 
 
2.  I>1 Current Set  1.00*In 
If DT 0.05 to 35.00*In  step 0.01*In 
If IDMT 0.05 to 4.00*In  step 0.01*In 
This setting determines the pick-up setting for first stage overcurrent element. 
3.  I>1 Time Delay  1.00 S  0s to 100s  step 0.01s 
This setting determines the time-delay for the definite time setting if selected for first stage overcurrent element. 
This time multiplier setting is used to adjust the operating time of the IEC / UK IDMT characteristic. 
5.  I>1 Time Dial  1.00  0.01 to 100  step 0.01s 
This time multiplier setting is used to adjust the operating time of the IEEE / US IDMT curves. 
6.  I>1 Reset Char  DT  DT/IDMT 
This setting determines the type of reset/release characteristics. IDMT applicable for IEEE curves only. 
This setting determines the reset/release time for IEEE IDMT characteristic 
8.  I>1 tRESET  1.00 S  0s to 100s   step 0.01s 
This setting determines the reset/release time for Definite Time (DT) and all IDMT curve 
9.  I>1 2H Blocking  Disabled  Enabled / Disabled 
This setting determines the enabling/disabling of blocking first stage overcurrent element due to presence of inrush current. 
 If I>1 Blocking and 2nd Harmonic settings are enabled, then (I>1) trip command will be blocked in case 2nd harmonics content in any 
phase is above the 2ndHarm Thresh. and fundamental current is below I> lift 2H setting . (Set in SYSTEM CONFIG Menu.) 
2.12.2.2  I>2 Function 
Sr. No  Parameter  Default setting  Setting Range  
1.  I>2 Function  IEC S Inverse  
Disabled / DT / IEC S Inverse / S Inverse 
1.3Sec / IEC V Inverse / IEC E Inverse / UK 
LT Inverse / IEEE M Inverse / IEEE V Inverse 
/ IEEE E Inverse / US Inverse / US  ST 
Inverse 
This setting determines the tripping characteristic for the second stage overcurrent element. 
2.  I>2 Current Set  1.00*In 
If DT 0.05 to 35.00*In  step 0.01*In 
If IDMT 0.05  to 4.00*In  step 0.01*In 
This setting determines the pick-up setting for second stage overcurrent element. 
3.  I>2 Time Delay  1.00 S  0s to 100s  step 0.01s 
This setting determines the time-delay for the definite time setting if selected for second stage overcurrent element. 
This time multiplier setting is used to adjust the operating time of the IEC / UK IDMT characteristic. 
5.  I>2 Time Dial  1.00  0.01 to 100  step 0.01 
This time multiplier setting is used to adjust the operating time of the IEEE / US IDMT curves. 
6.  I>2 Reset Char  DT  DT/IDMT 
This setting determines the type of reset/release characteristics. IDMT applicable for IEEE curves only. 
This setting determines the reset/release time for IEEE IDMT characteristic 
8.  I>2 tRESET  01.00 S  0s to 100s   step 0.01s 
This setting determines the reset/release time for Definite Time (DT) and all IDMT curve 
9.  I>2 2H Blocking  Disabled  Enabled / Disabled