2  FRONT PANEL 
 
Figure 1: Front panel 
Green LED indicates that the IED is in correct working order, and should be ON at all times. It 
turns red if the unit’s self-tests show there is an error in the hardware or software. 
2 
Amber LED flashes when the IED registers an alarm. This may be triggered by a fault, event or 
maintenance record. The LED flashes until the alarms have been accepted (read) by pressing 
VIEW RECORD function key, then changes to constantly ON. When the alarms are cleared, the 
LED switches OFF after pressing CLEAR key. 
Red LED switches ON when the IED issues a trip signal. When the faults are cleared, the LED 
switches OFF after pressing CLEAR key. 
4 
Amber LED flashes when the IED's protection is unavailable (eg. Setting error, ADC error 
detected by unit’s self-test etc) 
5  L5  Programmable dual colour LED 
6 
Programmable dual colour LED 
The LCD display is used to view the settings and parameters of the relay. 
Feather touch key to edit parameter settings. 
9  CLEAR  Feather touch key to clear the fault LED indications. 
Also used to discard the setting changes. 
Feather touch key is used for navigating through the menus/submenus and save the settings. 
11  ▲  Feather touch key is used to INCREASE the values and change the menu level or change 
between settings in a particular menu. 
▼
Feather touch key is used to DECREASE the values and to change the menu level or change 
between settings in a particular menu. 
►
Feather touch key is used to view the settings and to navigate through the menus and 
submenus.