2.3.8  Configuration Menu 
2.3.8.1  View/Edit Settings  
CONFIGURATION 
 
Password protected window for “CONFIGURATION’’ 
Restore Defaults, Active Settings, Copy From, Copy To, Setting Group 1 
(Enabled/Disabled), Setting Group 2 (Enabled/Disabled), System Config 
(Enabled/Disabled), Overcurrent (Enabled/Disabl
O/C (Enabled/Disabled), Broken Conductor (Enabled/Disabled), Earth 
Fault 1 (Enabled/Disabled), Earth Fault 2 (Enabled/Disabled), Thermal 
Overload (Enabled/Disabled), Cold Load Pickup (Enabled/Disabled), 
Measure’t Setup, UnderCurr Prot (En
(Enabled/Disabled) and Setting Values.  
Restore Defaults 
No Operation  
Editable setting 
By using the (5) or (6) key, Restore Defaults can be set as No 
Operation / All Settings / Setting Group 1 / Setting Group 2. 
Active Settings  
Group 1   
By using the (5) or (6) key, Active Setting can be set as Group 1 / 
Group 2. 
Copy From 
Group 1 
Editable setting 
By using the (5) or (6) key, Copy From can be set as Group 1 / 
Group 2. 
Copy To 
No Operation 
Editable setting 
By using the (5) or (6) key, Copy To can be set as No Operation / 
Group 1 / Group 2. 
 
Setting Group 1  
Enabled 
By using the (5) or (6) key, Setting Group 1 can be Enabled or 
Disabled.  
 
Setting Group 2  
Disabled 
By using the (5) or (6) key, Setting Group 2 can be Enabled or 
Disabled.  
 
System Config 
Disabled 
Editable setting 
By using the (5) or (6) key, System Configuration can be Enabled or 
Disabled.