Th State  %  Thermal state  
 
In the event of a fault, the type of the fault and fault current are displayed on LCD. The IED measures 
the fault current and stores it in the non-volatile memory. 
2.4  Opto Inputs 
The device supports 4 numbers of opto-inputs. The use of these opto-inputs depends on the 
application. There are a number of settings associated with the opto-inputs. 
The relays have programmable opto-isolated logic inputs, which can be assigned to any available 
function which are identified as Opto I/P 1 to Opto I/P 4.  These inputs are used to acquire status of 
external field signals such as CB close, CB open etc or can be programmed for function such as 
external reset, External trigger to DR etc. by using P50 Configurator as well as relay user interface. 
On the user interface, the Opto I/P can be assigned to any function from I/O configuration menu. The 
function can be assigned to any input by entering the values to them either 0 or 1 i.e. 0 = not assigned 
and 1 = assigned. 
The following are the list of functions, which can be assigning to digital input. 
Rem. Rst.  Function used to reset Latch type output contact and LED indication  
Function used to Initiate Breaker Fail  
Function used to enable Group 2 setting   
Ext  Trip  Function initiates the relay assigned for Gen. Trip to operate and trip the CB. 
DR Trig  Function used to trigger Disturbance Record  
CB (52A)  Status used to detect CB Close position 
CB (52B)  Status used to detect CB Open position 
Function used to block tripping of O/C stage 1 
Function used to block tripping of O/C stage 2 
Blk   I>3  Function used to block tripping of O/C stage 3 
Blk   I2>1  Function used to block tripping of NPS stage 1 
Blk   I2>2  Function used to block tripping of NPS stage 2 
Function used to block tripping of NPS stage 3 
Function used to block tripping of measured  E/F  stage 1 
Function used to block tripping of measured  E/F stage 2 
Blk   IN1>3  Function used to block tripping of measured  E/F stage 3 
Blk   IN2>1  Function used to block tripping of derived E/F stage 1 
Blk  IN2>2  Function used to block tripping of derived E/F stage 2 
Blk   IN2>3  Function used to block tripping of derived E/F stage 3 
Function used to block tripping of Broken Conductor 
Function used to block tripping of Thermal Overload 
Blk  I<  Function used to block tripping of Under Current 
TCS Trig  Status is used to monitor Trip Circuit Supervision 
 
 
The Digital inputs are suitable for accepting AC or DC auxiliary supply. The selection for AC or DC 
auxiliary supply is done from submenu Opto I/P under SYSTEM DATA menu.  
The DI can be selectable for different operating  voltage  (ordering  option)  depending  on the 
application requirement.