Thermal Alarm  
70% 
Editable setting 
By using the (5) or (6) key, Thermal Alarm can be set. The setting 
range is from 50% to 100% in steps of 1%.  
Time Constant 1 
10 
Editable setting 
By using the (5) or (6) key, Time Constant 1 can be set. The setting 
range is from 1 to 200 in steps of 1.  
K 
1.05 
By using the (5) or (6) key, K Constant can be set. The setting range 
is from 1 to 1.5 in steps of 0.01.  
2.3.16.9  Group1 – Cold Load Pickup Submenu 
2.3.16.9.1 
Edit Settings
 
GROUP 1 
 
Password protected window for “GROUP 1’’ settings: 
SYSTEM CONFIG, OVERCURRENT, NEG SEQUENCE O/C, BROKEN 
CONDUCTOR, EARTH FAULT 1, EARTH FAULT 2, THERMAL 
OVERLOAD, COLD LOAD PICKUP, UNDERCURRENT and CB FAIL. 
Note: Group 1 Setting will be seen only when it is enabled in 
Configuration setting.. 
COLD LOAD PKP 
 
Password protected window for Cold Load Pickup i.e. tcold Time Delay, 
tclp Time Delay, I>1 Status, I>2 Status, I>3 Status, IN1>1 Status, IN1>2 
Status, IN1>3 Status, IN2>1 Status, IN2>2 Status and IN2>3 Status. 
tcold Time Delay 
7200 S  
Editable setting 
By using the (5) or (6) key, tcold Time Delay can be set. The setting 
range is from 0 to 14400s in steps of 1s.  
tclp Time Delay 
7200 S  
Editable setting 
By using the (5) or (6) key, tclp Time Delay can be set. The setting 
range is from 0 to 14400s in steps of 1s.  
I>1 Status    
Enabled 
By using the (5) or (6) key, I>1 Status can be Enabled / Blocked. 
I>2 Status    
Enabled 
Editable setting 
By using the (5) or (6) key, I>2 Status can be Enabled / Blocked.