7 Protection Parameter Settings 
 
 
2.  CB Fail Timer  0.1 S  0s to 50s step 0.01s 
This setting sets the time delay in which the CB opening must be detected. 
3.  CBF Reset  CB Open + I< 
2=CB Open + I< 
3=Prot Reset + I< 
4= CB Open 
This setting determines the elements that will reset the CB fail timer for CB Failures 
4.  I<  1.00*In  0.05*In to 3.20*In  step 0.01    
This setting determines the current threshold, which will reset the CB Fail timer for Overcurrent based protection 
5.  IN<  1.00*In  0.05*In to 3.20*In  step 0.01    
This setting determines the current threshold, which will reset the CB Fail timer for Earth fault based protection 
This setting for removing phase overcurrent start signal following CBF operation 
7.  Remove IN> Start  Disabled   Disabled / Enabled 
This setting for removing earth overcurrent start signal following CBF operation 
2.12.11  VIEW RECORDS 
1.  Fault Record  Display the Records of fault i.e. parameter value, flag of fault & date and time  of Fault  
Display of all digital events with time stamping (max 512 events) 
Display of error generated by relay if any, in case of failure of hardware  
4.  Alarm Record  Display of alarm generated by relay & date and time of generated alarm.