AquaTrans™ AT600 User’s Manual 29
Chapter 3. Wiring the AT600 Electronics
3.7 Wiring the Frequency/Totalizer/Alarm Output
The AT600 can accommodate up to two digital outputs. Each of these outputs can be configured as either a
totalizer, frequency or alarm output (see “Programming Digital Communications” on page 61 for instructions).
Each totalizer/frequency/alarm output requires a twisted pair cable. Wire the terminal block as shown in
Figure 23 on page 23 and Figure 28 below.
Figure 28: Totalizer/Frequency/Alarm Output Wiring
Model AT600
Totalizer/Frequency Counter
or Alarm Detector
PIN: 9/B
PIN: 8/A
C: Isolated Return
(Int. Pwr. Sup.)
Volts +
(Common)
Volts -
10 Kohms)
(minimum
Load
Max. Current:
Max. Voltage:
Isolation Voltage:
Max. Load Power:
1A
100 V
500 V
2W IN