MDS 05-6632A01, Rev. F MDS Orbit MCR/ECR Technical Manual 321
Click ‘Add’ at Netmon --->Basic Config / General and create an operation with a descriptive name, say,
NX-LINK-CHECK.
The above configuration will indicate that the link is down (or up) if 6 successive pings fail (or succeed).
Enabled - Whether or not to run this operation
Type - Type of monitor operation
Icmp Echo Monitor
- Dst Host - Destination IP address or DNS name to send icmp-echo to.
- Src Address - Source address to use for icmp-echo request
- Interval - Time interval (in seconds) between icmp-echo requests. Value range [1..86400]
DEFAULT=5
- Timeout - Time to wait (in milliseconds) for icmp-echo response. Value range [1..5000]
DEFAULT=2000