Chapter 5 Detailed Descriptions of I/O Modules
GFK-2958E RSTi-EP User Manual 103
Specifications EP-1318
Process, parameter and diagnostic data depend on the network
adapter used (refer to the table in the section, Order and
Arrangement of the Modules)
RSTi-EP I/O communication bus
Type 1 and Type 3 sensors as per IEC 61131-2
Input delay adjustable from 0 to 40 ms (PROFIBUS-DP to 20 ms)
max. 2 A per plug, total max. 8 A
Reverse polarity protection
Individual channel diagnosis
Current consumption from system current path
I
SYS
Current consumption from input current path I
IN
30 mA + sensor supply current
For additional general data, refer to the section General Technical Data for I/O Modules.
Overview of the Editable Parameter EP-1318
no (0) / 0,3 ms (1) (not at PROFIBUS-DP) / 3 ms (2) / 10
ms (3) / 20 ms (4) / 40 ms (5) (not at PROFIBUS-DP)