Chapter 8 Commissioning
GFK-2958E RSTi-EP User Manual 355
Enabled Alarms
Pull Plug Alarm
Editable or read-only, depending on theGSD file. When this box is checked, a slot signals
the withdrawal of a module or the insertion of a module.
Process Alarm
Editable or read-only, depending on the GSD file. When this check box is checked, a
process alarm signals the occurrence of an event in the connected process. For example,
the event may be "upper limit value exceeded."
Diagnostic Alarm
Editable or read-only, depending on the GSD file. When this check box is checked, a
diagnostic alarm signals an event within a slot. For example, events may be over
temperature or short circuit.
Manufacture Alarm
Editable or read-only, depending on the GSD file. When this box is checked, manufacturer-
specific alarms are enabled.
Status Alarm
Editable or read-only, depending on the GSD file. When this check box is checked, a status
alarm signals a change in the state (such as run, stop, or ready) of a module.
Update Alarm
Editable or read-only, depending on the GSD file. When this check box is checked, an
update alarm signals the change of a parameter in a slot, for example, by a local operation
or remote access.
8.4 Configuring EPXECT001
To configure EPXECT001
1. Open CoDeSys software, right-click CoDeSys and select Add Device.
2. From the Add Device dialog box, click to select Append device, then double-click EtherCAT
Master.