GFK-2958E RSTi-EP User Manual 16
1.6 General Technical Data for I/O Modules
Conductor cross-section
0.14 – 1.5 mm
2
(AWG 16 – 26)
Conductor cross-section
0.14 – 0.35 mm2 (AWG 22 – 26)
4.72 in (120.0 mm)
w/ release lever: 128.0 mm (5.04 in)
Protection class
(DIN EN 60529)
Flammability rating UL 94
-20°C to +60°C (- 4 to +140 °F)
-40°C to +85°C (- 40 to +185 °F)
Operation, storage, transport
5 % to 95 %, non-condensing
as per IEC 61131-2
≥ 795 hPa (altitude ≤ 2000 m)
as per IEC 61131-2
≥ 700 hPa (altitude ≤ 3000 m)
as per IEC 61131-2
5 Hz ≤ f ≤ 8.4 Hz: 3.5-mm amplitude as per IEC 60068-2-6
8.4 Hz ≤ f ≤ 150 Hz: 1-g acceleration as per IEC 60068-2-6
15 g over 11 ms, half sinewave, as per IEC 60068-2-27
max. 28.8 V within one channel
500 V DC field/system
UL 508, CSA C22.2 No. 0-M91
C
UL
US
Hazardous Locations
Class 1 Division 2, Gr. A, B, C, D
ISA 12.12.01: 2007
CSA C22.2 No. 213-M1987 (Reaffirmed 2008)
Potentially explosive atmosphere
Zone 2
†
ATEX Directive 2014/34/EU
EN 60079-0:2012+A11:2013 and EN 60079-
15:2010
IEC 60079-0:2011 and
IEC 60079-15:2010
EN61000-6-2: 2005, EN61000-6-4: 2007 +
A1:2011, (partial standards as per the
requirements of EN61131‑2: 2007)
47 CFR 15: 2011 (Class A)
†
Unless otherwise noted within the product-specific technical data.
All product-specific technical data is available in the corresponding product description in Chapter 5, Detailed Descriptions
of I/O Modules.