Chapter 5 Detailed Descriptions of I/O Modules
GFK-2958E RSTi-EP User Manual 154
5.13 Digital Output Module EP- 2714
Digital Relay Output Module EP-2714 Connection Diagram EP-2714
The digital relay output module EP-2714 can control up to 4 discrete outputs, each with a maximum
of 6 A. Each connector features a potential-free changeover contact. The relay coils are supplied with
power from the output current path (I
OUT
).
Caution
When using relay modules EP-2714 in explosive atmosphere:
Condensation shall be avoided.
If the switching voltage exceeds 63 V, a transient protection device
shall be provided that limits the transients to a peak voltage of 500 V
or less.