GFK-2958E RSTi-EP User Manual 35
3.8.1 Calculation of Feedback Energy
The feedback energy for a digital output module can be calculated as follows:
P = Σ
all channels
1/2 n
i
* L
i
* I
i
²
Feedback energy of the module
Switching cycles of Channel i in 1/seconds
Feedback energy when shutting off Channel i during a shutdown
procedure
Current through the load connected to Channel i
Inductance of the load connected to Channel i
Once the maximum permissible feedback energy E
max
is reached, the module shuts down.
Maximum Feedback Energy Varies with Ambient Temperature