Minimum Distance to Switch Cabinet Door (with/without Swivel Marker)
6.1.8 Calculation of Space Requirements
The space requirements for a RSTi-EP station with n modules (horizontal installation) is calculated as
follows:
Height: 120 mm (4.72”)
+ 2 x 40 mm (1.57”) distances at top and bottom
= 200 mm (7.87”)
Width: 8 mm (1.57” ) end bracket
+ 52 mm (2.05”) bus network adapter
+ n x 11.5 mm (0.45”) n modules
+ 11.5 mm (0.45”) end plate and end bracket
+ 2 x 20 mm (0.79”) distances to the sides
= 111.5 mm (4.39”) + n x 11.5 mm (0.45”)
For vertical installation interchange height and width. When calculating the width for vertical
installation, 4.5 mm (0.18”) must be added for the end bracket.
6.1.9 Installation Sequence
A RSTi-EP station may only be installed in this sequence (starting from the left/bottom):
End bracket
Bus network adapter
Up to 64 active modules
End plate and end bracket
If the station has already been configured, proceed to the corresponding installation drawing. If you
are configuring the station yourself, observe the following instructions:
Observe the maximum current carrying capacity (refer to the section, Current Demand and
Power Supply).
Furthermore, the modules may be arranged in any sequence. In order to configure the
station as clearly as possible, it is recommended to arrange the modules according to their
function.