Chapter 4 Detailed Descriptions of the Fieldbus Network Adapters
GFK-2958E RSTi-EP User Manual 81
4.4.4 Configuration of the IP Address
The web server can be used to define whether a static IP address shall be used or the address shall
be assigned automatically (DHCP/BootP).
Network adapters using firmware version 01.xx.xx are preset to the static IP address 192.168.0.222.
Network adapters using firmware version 02.00.00 or higher will by default send a DHCP discover
first. If no assignment by a DHCP server follows during the next 30 seconds, the static IP address
192.168.0.222 will be set.
Overview of the Editable Parameters EPXMBE001/EPXMBE101
Waiting time, 1 to 1000 s
0 (disabled) / Value from 1 to 65535
†
(except for 80 and 161)
Modbus Dual LAN Mode
(EPXMBE101 ony)
†
192.168.1.202; 192.168.2.202,
192.168.3.202, 192.168.4.202,
192.168.5.202
no, refer to register 0x113C – 0x113F Save
Module Parameters
Watchdog time in steps of 10 ms
0 *10 ms, refer to register 0x1120 MODBUS
DATA EXCHANGE watchdog, predefined time
Modbus Connection
Timeout
Connection watchdog time in sec
1 s, refer to register 0x1131 MODBUS
CONNECTION Timeout in Sec
Write access in multi-
client operation
write for all, 1stWr1stServe,
1stConn1stServe
write for all, refer to register 0x1031
MODBUS CONNECTION Mode Register
Check reference list
before exchanging data
disabled, refer to register 0x1132 Check
Reference List prior to Data Exchange
refer to register 0x1133 Process Alarm
refer to register 0x1134 Diagnostic Alarm
Behavior of outputs on
fieldbus error
All outputs off / Enable substitute values /
Hold last value
All outputs off, refer to register 0x1135 Field
Bus or Reference List Error Behavior
Module behavior on hot
swap
Continue data exchange / Behavior like
fieldbus error
Continue data exchange, refer to register
0x1136 Module Removal Behavior
Motorola, refer to register 0x1137 Data
Format
Force mode unlocked / Force mode locked
Force mode unlocked, refer to register
General Contact Information
†
Change requires restart of the network adapter.
#
In Dual LAN Mode (EPXMBE101 only) parameterizable for each Ethernet Port on the Module
1
Parameter “Additional TCP port“
Another TCP port additionally to the standard port (502) can be enabled using this parameter. Apart
from the values 80 (reserved for http) and 161 (reserved for SNMP) every number from 1 to 65535 can
be used. Value 0 deactivates the port. The standard port 502 will remain open in any case.