Chapter 4 Detailed Descriptions of the Fieldbus Network Adapters
GFK-2958E RSTi-EP User Manual 82
2
Parameter “Save module parameters“ in the web server
The choice Yes or Standard cannot be displayed in the web server, caused by the data structure of
this parameter. The display will be reset to No anytime.
Option Yes: The current image of all module parameters is saved in the network adapter and will be
sent to the modules again during the Network adapter’s next restart. Subsequent changes of the
module parameters are considered and saved only if the option Yes will be chosen again.
Option Standard: The default parameters will be loaded to the modules immediately. Subsequent
changes of the module parameters are possible, but they will get loss during the network adapter’s
next restart.
Parameter “Restore module parameters“
This parameter is not editable. It will be automatically set to Yes as soon as the network adapter will
have sent saved parameter data to the modules.
Register Structure
(ro: read only = input register, rw: read write = holding register, wo: Write only = holding register)
Register address
(in hex)
Access
Data width
Description
Remarks
0x0000 0x01FF
ro
Module-
dependent
Packed process data for inputs
byte granularly
0x0800 0x09FF
rw
Module-
dependent
Packed process data for outputs
byte granularly
0x1000 x1006
ro
Byte
Network adapter identifier
0x100C
ro
Word
Network adapter status
Bit assignment as
with EPXETC001
0x1010
ro
Word
Process image length in bits for the output
modules
0x1011
ro
Word
Process image length in bits for the input modules
0x1017
ro
Word
Register mapping revision
0x1018 0x101B
ro
Byte
Collective diagnostics message for I/O modules
(1 bit per I/O module)
0x101C 0x101F
ro
Byte
Collective process alarm message for I/O modules
(1 bit per I/O module)
0x1028 0x102F
ro
Byte
Module status (2 bits per I/O module) 00 = module
OK, 01 = module error 10 = incorrect module 11 =
module not plugged in
Structure as in
PROFIBUS module
status
0x1030
ro
Word
MODBUS DATA EXCHANGE watchdog, current
time (x*10 ms) 0 = watchdog has expired 0xFFFF =
watchdog deactivated
Time still remaining
for monitoring the
exchange of process
data
0x1120
rw
Word
MODBUS DATA EXCHANGE watchdog, predefined
time (x*10 ms), default = 0 ms (no watchdog
active)
Time for monitoring
the exchange of
process data
0x1121
rw
Word
MODBUS DATA EXCHANGE watchdog reset
register
Bit0 = 1: watchdog reset at predefined time
Bit8 = 1: restart after expired watchdog
Bit 0: reset watchdog
while it is running
(retrigger)
Bit 8: restart of
expired watchdog
0x1122
rw
DWord
Lock of the Force Mode via Webserver
LOCK to lock,
FREE to unlock
0x1124 0x1125
rw
Long
Changing IP Address 1 via Fieldbus
0x1126 0x1127
rw
Long
Changing Subnet Mask 1 via Fieldbus
0x1128 0x1129
rw
Long
Changing Gateway 1 via Fieldbus
0x1130
rw
Word
MODBUS CONNECTION mode register
0x1131
rw
Word
MODBUS CONNECTION timeout in sec.
Default = 1 (0 not allowed)
0x1132
rw
Word
Check the reference list before data exchange