Chapter 4 Detailed Descriptions of the Fieldbus Network Adapters
GFK-2958E RSTi-EP User Manual 83
0x0000 = disable, 0x0001 = enable
0x1133
rw
Word
Process alarm 0x0000 = disable, 0x0001 = enable
0x1134
rw
Word
Diagnostics alarm 0x0000 = disable, 0x0001 =
enable
0x1135
rw
Word
Behavior in case of field bus error and reference
list error
0x0000 = all outputs to 0, 0x0001 = set error
values
0x0002 = retain process data
0x1136
rw
Word
Behavior when module removed
0x0000 = process data continues to run
0x0001 = behavior as with field bus error
0x1137
rw
Word
Data format 0x0000 = Motorola, 0x0001 = Intel
0x113C 0x113D
wo
Long
Restore module parameters
Motorola =“LOAD”, Intel =“DAOL”
Corresponds to the
“DEFAULT” in the web
server
0x113E 0x113F
wo
Long
Save module parameters
Motorola =“SAVE”, Intel =“EVAS”
Corresponds to
“SAVE” in the web
server
0x1140 0x1141
rw
Long
Changing IP Address 2 via Fieldbus
These registers only
available with
EPXMBE101
0x1142 0x1143
rw
Long
Changing Subnet Mask 2 via Fieldbus
0x1144 0x1145
rw
Long
Changing Gateway 2 via Fieldbus
0x27FE
ro
Word
Number of entries in the current module list
0x27FF
ro
Word
Number of entries in the reference module list
0x2800 0x287F
rw
Long
Reference module list (max. 64 modules per
station * 2 registers per module)
There must always be
2, 4, 6 etc. registers
transferred
0x2A00 0x2A7F
ro
Long
Current module list (max. 64 modules per station *
2 registers per module)
There must always be
2, 4, 6 etc. registers
transferred
0x8000 0x87FF
ro
Module
Process data inputs (max. 64 modules per station
* 32 registers per module)
0x9000 0x97FF
rw
Module
Process data outputs (max. 64 modules per
station * 32 registers per module)
0xA000 0xA7FF
ro
Byte
Diagnostics (max. 64 modules per station * 32
registers per module)
Confirmation by
readout
0xB000 0xB7FF
ro
Byte
Process alarms (max. 64 modules per station * 32
registers per module)
Confirmation by
readout
0xC000 - 0xC7FF
(Firmware 01.xx.xx)
0xC000 - 0xFFFF
(Firmware 02.00.00
or higher)
rw
Byte
Module parameters (Firmware 01.xx.xx:
max. 64 modules per station * 32 registers per
module;
Firmware 02.00.00 or higher:
max. 64 modules per station * 256 registers per
module)
Note: If the user wants to access the DWORD for EP-5111, EP-5112, EP-5212, EP-5442 and EP-5422 modules use
SWAP_DWORD function block.
Implemented Modbus Functions
Function
code no.
Function
Description
1
Read Coils
Reading of output bits in the range of 0x0800 0x0FFF
2
Read Discrete Inputs
Reading of input bits in the range of 0x0000 0x07FF
3
Read Holding Registers
Reading of multiple holding registers
4
Read Input Registers
Reading of multiple input registers
5
Write Single Coil
Writing of an individual output bit in the range of 0x0800
0x0FFF
6
Write Single Registers
Writing of individual holding registers
15
Write Multiple Coils
Writing of output bits in the range of 0x0800 0x0FFF