GFK-2958E RSTi-EP User Manual 161
The counter module EP-5111 can read one square-wave signal (1 channel) (for example, from an
incremental encoder) with a maximum input frequency of 100 kHz. The 32-bit counter can count up
or down within a predetermined range of values.
The counter can be controlled using software or externally through the latch, gate, and reset inputs.
A digital output can be parameterized to be activated immediately upon either dropping below,
meeting, or exceeding the set comparison value. An overrun time can be provided with the
parameter Pulse duration. Thus the PLC will recognize even signals succeeding extremely fast.
In mode Pulse and Direction, channel CH0 A is used as the input and channel CH0 B as a direction-
determining input. In incremental mode, an incremental encoder with track A and B can be
connected. A status LED is assigned to each channel. The module electronics supply the connected
sensors with power from the input current path (I
IN
).
LED Indicators EP-5111