Chapter 5 Detailed Descriptions of I/O Modules
GFK-2958E RSTi-EP User Manual 204
Process Data
Inputs EP-5212
Byte
Format
Name
Bit
Function when active
Remark
IB0 ... IB3
Double word
Counter 0:
Counter value
Channel 0: Currently measured value
of period duration multiplied by 125 ns
results in the current period duration
in μs
IB4 ... IB7
Double word
Counter 1:
Counter value
Channel 0: Number of rising edges
within the current measurement cycle
IB8 ... IB11
Double word
Counter 0:
Counter status
Channel 1: Currently measured value
of period duration multiplied by 125 ns
results in the current period duration
in μs
IB12 ... IB15
Double word
Counter 1:
Counter status
Channel 1: Number of rising edges
within the current measurement cycle
IB16
Word
Channel 0:
Status
IX16.0
... 16.7
reserved
IB17
IX17.0
Measurement active
IX17.1
... 17.7
reserved
IB18
Word
Channel 1:
Status
IX18.0
... 18.7
reserved
IB19
IX19.0
Measurement active
IX19.1
... 19.7
reserved
Internal process data mapping with data format Standard. Depending on the fieldbus specification and the data format of
the communicating fieldbus components the bytes and/or words can be reversed during data transfer.
Process Data
Outputs EP-5212
Byte
Format
Name
Bit
Function when
edge 0-1
Remark
QB0 ... QB3
Double word
Channel 0:
Measurement
cycle period
Channel 0: Preset value of the
measurement cycle period (23 Bit)
QB4 ... QB7
Double word
Channel 1:
Measurement
cycle period
Channel 1: Preset value of the
measurement cycle period (23 Bit)
QB8
Word
Channel 0:
Control word
QX8.0 -
QX8.7
reserved
QB9
QX9.0
Measurement start
QX9.1
Measurement stop
QX9.2 -
9.7
reserved
QB10
Word
Channel 1:
Control word
QX10.0
- X10.7
reserved
QB11
QX11.0
Measurement start
QX11.1
Measurement stop
QX11.2
- 11.7
reserved
Internal process data mapping with data format Standard. Depending on the fieldbus specification and the data format of
the communicating fieldbus components the bytes and/or words can be reversed during data transfer.