Chapter 5 Detailed Descriptions of I/O Modules
GFK-2958E RSTi-EP User Manual 250
Process Data
Inputs EP-3124
Byte
Format
Description
Remarks
IB0
Word
AI0
IB1
IB2
Word
AI1
IB3
IB4
Word
AI2
IB5
IB6
Word
AI3
IB7
Internal process data mapping with data format “Standard”. Depending on the fieldbus specification and the data
format of the communicating fieldbus components the bytes and/or words can be reversed during data transfer.
Measurement Range EP-3124
Measurement
range
Current (I) /
Voltage (U)
Decimal (D)
Hexadecimal
Range
Conversion
0 20 mA
23.52 mA
32511
0x7EFF
Overloading
D = 27648 x I / 20
I = D x 20 / 27648
20 mA
27648
0x6C00
Nominal range
10 mA
13824
0x3600
0 mA
0
0x0000
4 20 mA
22.81 mA
32511
0x7EFF
Overloading
D = 27648 x (I 4) / 16
I= D x 16 / 27648 + 4
20 mA
27648
0x6C00
Nominal range
12 mA
13824
0x3600
4 mA
0
0x0000
1.19 mA
-4864
0xED00
Underloading
0 10 V
11.76 V
32511
0x7EFFh
Overloading
D = 27648 x U/10
I = D x 10 / 27648
10 V
27648
0x6C00
Nominal range
5 V
13824
0x3600
0 V
0
0x0000
±10 V
11.76 V
32511
0x7EFF
Overloading
D = 27648 x U / 10
U = D x 10 / 27648
10 V
27648
0x6C00
Nominal range
5 V
13824
0x3600
0 V
0
0x0000
-5 V
-13824
0xCA00
-10 V
-27648
0x9400
-11.76 V
-32511
0x8100
Underloading
2 - 10 V
11.41 V
32511
0x7EFF
Overloading
D = 27648 x (U 2) / 8
U = D x 8 / 27648 + 2
10 V
27648
0x6C00
Nominal range
6 V
13824
0x3600
2 V
0
0x0000
0.59 V
-4864
0xED00
Underloading
1 - 5 V
5.7 V
32511
0x7EFF
Overloading
D = 27648 x (U 1) / 4
U = D x 4 / 27648 + 1
5 V
27648
0x6C00
Nominal range
3 V
13824
0x3600
1 V
0
0x0000
0.30 V
-4864
0xED00
Underloading