Chapter 5 Detailed Descriptions of I/O Modules
GFK-2958E RSTi-EP User Manual 267
Process Data
Inputs EP-4164
Byte
Format
Description
Remarks
QB0
Word
AO0
QB1
QB2
Word
AO1
QB3
QB4
Word
AO2
QB5
QB6
Word
AO3
QB7
Internal process data mapping with data format “Standard”. Depending on the fieldbus specification and the data
format of the communicating fieldbus components the bytes and/or words can be reversed during data transfer.
Value Range
EP-4164
Measurement
range
Current (I) /
Voltage (U)
Decimal (D)
Hexadecimal
Range
Conversion
0 20 mA
23.52 mA
32511
0x7EFF
Overloading
D = 27648 x I / 20
I = D x 20 / 27648
20 mA
27648
0x6C00
Nominal range
10 mA
13824
0x3600
0 mA
0
0x0000
4 20 mA
22.81 mA
32511
0x7EFF
Overloading
D = 27648 x (I 4) / 16
I= D x 16 / 27648 + 4
20 mA
27648
0x6C00
Nominal range
12 mA
13824
0x3600
4 mA
0
0x0000
1.19 mA
-4864
0xED00
Underloading
0 10 V
11.76 V
32511
0x7EFFh
Overloading
D = 27648 x U/10
I = D x 10 / 27648
10 V
27648
0x6C00
Nominal range
5 V
13824
0x3600
0 V
0
0x0000
0 V
0
0x0000
±10 V
11.76 V
32511
0x7EFF
Overloading
D = 27648 x U / 10
U = D x 10 / 27648
10 V
27648
0x6C00
Nominal range
5 V
13824
0x3600
0 V
0
0x0000
-5 V
-13824
0xCA00
-10 V
-27648
0x9400
-11.76 V
-32511
0x8100
Underloading
2 - 10 V
11.41 V
32511
0x7EFF
Overloading
D = 27648 x (U 2) / 8
U = D x 8 / 27648 + 2
10 V
27648
0x6C00
Nominal range
6 V
13824
0x3600
2 V
0
0x0000
0.59 V
-4864
0xED00
Underloading

Table of Contents