Chapter 5 Detailed Descriptions of I/O Modules
GFK-2958E RSTi-EP User Manual 273
Diagnostic Data EP-4264
Name
Bytes
Bit
Description
Default
Error Channel 0
11
0
Parameter Error
1
Overtemperature
2
Overload
3
Error
4
Line break
5-7
Reserved
0
Error channel 1
12
0
Parameter Error
1
Overtemperature
2
Overload
3
Error
4
Line break
5-7
Reserved
0
Error channel 2
13
0
Parameter Error
1
Overtemperature
2
Overload
3
Error
4
Line break
5-7
Reserved
0
Error channel 3
14
0
Parameter Error
1
Overtemperature
2
Overload
3
Error
4
Line break
5-7
Reserved
0
Channel 4 error
to Channel 31 error
15-42
0-7
Reserved
0
Time stamp
43-46
Time stamp [μs] (32 bit)
Process Data
Inputs EP-4264
Byte
Format
Description
Remarks
QB0
Word
AO0
QB1
QB2
Word
AO1
QB3
QB4
Word
AO2
QB5
QB6
Word
AO3
QB7
Internal process data mapping with data format Standard. Depending on the fieldbus specification and the data
format of the communicating fieldbus components the bytes and/or words can be reversed during data transfer