Chapter 5 Detailed Descriptions of I/O Modules
GFK-2958E RSTi-EP User Manual 283
Temperature Measurement Range EP-3704
Measurement
range
Value in °C
0.1 ° resolution
Value in °F
0.1 °/digit
Value in K
0.1 K/digit
Range
Pt100
-2000 to 8500
-3280 to 15620
732 to 11232
-200 °C to +850 °C
-2040
-3352
692
Underloading
8540
15692
11272
Overloading
32767
32767
32767
Line break
Pt200
-2000 to 8500
-3280 to 15620
732 to 11232
-200 °C to +850 °C
-2040
-3352
692
Underloading
8540
15692
11272
Overloading
32767
32767
32767
Line break
Pt500
-2000 to 8500
-3280 to 15620
732 to 11232
-200 °C to +850 °C
-2040
-3352
692
Underloading
8540
15692
11272
Overloading
32767
32767
32767
Line break
Pt1000
-2000 to 8500
-3280 to 15620
732 to 11232
-200 °C to +850 °C
-2040
-3352
692
Underloading
8540
15692
11272
Overloading
32767
32767
32767
Line break
Ni100
-600 to +2500
-760 to 4820
2132 to 5232
-60 °C to 250 °C
-640
-832
2092
Underloading
2540
4892
5272
Overloading
32767
32767
32767
Line break
Ni120
-800 to +2600
-1120 to +5000
1932 to 5332
-80 °C to 260 °C
-840
-1192
1892
Underloading
2640
5072
5372
Overloading
32767
32767
32767
Line break
Ni200
-600 to +2500
-760 to 4820
2132 to 5232
-60 °C to 250 °C
-640
-832
2092
Underloading
2540
4892
5272
Overloading
32767
32767
32767
Line break
Ni500
-600 to +2500
-760 to 4820
2132 to 5232
-60 °C to 250 °C
-640
-832
2092
Underloading
2540
4892
5272
Overloading
32767
32767
32767
Line break
Ni1000
-600 to +2500
-760 to 4820
2132 to 5232
-60 °C to 250 °C
-640
-832
2092
Underloading
2540
4892
5272
Overloading
32767
32767
32767
Line break
Cu10
-1000 to +2600
-1480 to 5000
1732 to 5332
-100 °C to 260 °C
-1040
-1552
1692
Underloading
2640
5072
5372
Overloading
32767
32767
32767
Line break