Chapter 6 Installation
GFK-2958E RSTi-EP User Manual 319
1. On the left side of the installation site, place an end bracket on the DIN rail with the exterior of
the bracket facing left and screw it down tightly (using a 3-mm (0.1”) screwdriver).
Attaching the End Bracket
Note: When installing the RSTi-EP products, make sure that you listen for the double click:
a) When snapping onto the DIN rail
b) When pushing together with the neighboring module.
The modules are in the correct position and the connection is made only when both snapping
noises are heard.
Caution
Improper installation may prevent grounding.
The grounding of the modules and network adapters is only ensured if the
FE spring at the bottom is in contact with the DIN rail.
During installation, make sure that both release levers on the bus network
adapter and all release levers on the modules are closed before snapping
onto the DIN rail.
Release Lever Closed