Chapter 12 LED Indicators and Troubleshooting
GFK-2958E RSTi-EP User Manual 405
Module
LED
Status
Recommended action
EP-3804, EP-3704
Status
LED
Red:
Error in supply voltage at input
current path
Communication error on the
system bus
There is a new diagnostic
message
Channel error
Firmware error
Check that the module has been snapped
into place properly
Check the supply voltage
Check channel error
Check firmware, update firmware as
necessary
Status LED off and all other LEDs
red: Error in the bus network
adapter power supply
Check the bus network adapter supply
voltage
Channel
LED
1.1-4.1
Red:
Input signal outside permissible
range
Line break
Cold-junction compensation error
(EP-3804 only)
System bus cannot be accessed
(for example, caused by
interruption of the bus network
adapter power supply)
Check the input signal, the cabling and, if
necessary, the sensor for external cold-
junction compensation.
Check the bus network adapter supply
voltage
Analog output modules
EP-4164, EP-4264
Status
LED
Red:
Error in supply voltage
Communication error
Channel error
Check that the module has been snapped
into place properly
Check the supply voltage
Check the channel error
Status LED off and all other LEDs
red: Error in the bus network
adapter power supply
Check the bus network adapter supply
voltage
Channel
LED
1.1-4.1
Red:
Overload in voltage mode
Broken line in current mode
System bus cannot be accessed
(for example, caused by
interruption of the bus network
adapter power supply)
Check the connected load, check the cabling,
Check the bus network adapter supply
voltage

Table of Contents